Operation
975-0125-02-01 219
Equalizing Batteries
To equalize your batteries:
1. Turn off or disconnect all loads on the battery.
The voltage applied to the battery during equalization may damage your
electronic equipment. As well, equalization wont proceed correctly if loads
are drawing current from the battery.
2. Check electrolyte level.
Fill with distilled water if the electrolyte level is low.
3. To request the equalization charge, ensure the Charger switch is enabled, and
then scroll to the Equalize setting on the System Control Panel.
4. In the MS2000 home menu, highlight Equalize, as shown in
Figure 2-12.
When you select On, the equalization confirmation warning appears, as shown in
Figure 2-13.
Important:
Equalization will be carried out after an absorption charge.
Equalization only runs for 60 minutes and may need to be restarted if the
specific gravity is still uneven.
Figure 2-12
Equalize On
Seitenansicht 48